冰蓄冷整裝機
ICE STORAGE PACKAGED
將特殊介質(zhì)封裝在儲能芯內(nèi),并將儲能芯安裝于容器中,在低溫狀態(tài)下結(jié)冰蓄存冷量。適用于商城、酒店、藥廠、化工廠、電子車間等場所谷電制冷、蓄冷、峰電使用,實現(xiàn)減碳降費的目的。
The special medium is encapsulated in the energy storage core, and the energy storage core is installed in thecontainer to freeze and store cold energy at low temperature. It is applicable to the use of valley cooling, coldstorage and peak power in shopping malls, hotels, pharmaceutical plants, chemical plants, electronic workshopsand other places to achieve the purpose of reducing carbon and costs.
冰蓄冷整裝機優(yōu)勢
Advantages of ice storage packaged machine
A:換熱流道專業(yè)設(shè)計,阻力小,換熱能力強。
B:內(nèi)融冰技術(shù)、無蓄冰槽、無冰盤管,蓄冰能力提高30%以上。
C:整裝設(shè)計、標定工況、適配性強,無須專業(yè)設(shè)計。
D:合成高導(dǎo)熱材料,釋冷速率快。
A: The heat exchange runner is designed professionally, with small resistance and strong heat exchange capacity.
B: Internal ice melting technology, no ice storage tank, no ice coil, and the ice storage capacity is increased by more than 30%.
C: Integrated design, calibration conditions, strong adaptability, no professional design.
D: Synthesis of high thermal conductivity materials, fast cooling release rate.
冰蓄冷整裝機參數(shù)
ICE STORAGE PACKAGED
冰蓄冷整裝機 | 單位 | 蓄冷 | |
型號 | GESPC-1800+ | ||
最大名義菅冷量 | kWh | 1800 | |
谷電時段蓄冷時間 | h | 8 | |
小時放冷量 | kw | 225 | |
相變溫度 | ℃ | -4 | |
蓄冷進出口溫度 | ℃ | 2 / -4 | |
放冷進出口溫度 | ℃ | 12→7 | |
流量 | 32.71 | ||
水側(cè)壓力損失 | kPa | 76.8 | |
推薦流速 | m/s | 1.582 | |
輸入功率 | kw | 循環(huán)水泵輸入功率(選配) | |
運行工況 | 推薦蓄冷時間 | 當(dāng)?shù)毓入姇r段 | |
推薦放冷時間 | 當(dāng)?shù)胤咫?尖峰時段 | ||
計量單位 | 電量/冷量 | ||
控制方式 | 系統(tǒng)聯(lián)機控制/程序自動 | ||
外形尺寸 | mm | 6058*2580*2591 | |
運行總重(kg) | kg | 31000 |
冰蓄冷整裝機配套雙工況制冷機組參數(shù)表(推薦)
蓄冰工況參數(shù)表
CVHE/G
壓縮機型號 | 670 | 780 | 1100 | 1100 | 1100 | 1100 | ||||||||
電機型號 | 491 | 623 | 718 | 801 | 894 | 894 | ||||||||
葉輪型號 | 318 | 317 | 322 | 318 | 318 | 323 | ||||||||
筒體組合 | 080SS | 080SL | 080L142L | 080L142L | 142LL | 142LL | ||||||||
狀態(tài) | 白天 | 夜晚 | 白天 | 夜晚 | 白天 | 夜晚 | 白天 | 夜晚 | 白天 | 夜晚 | 白天 | 夜晚 | ||
制冷量 | Ton | 600 | 438.3 | 800 | 508 | 1000 | 727.9 | 1100 | 707.4 | 1200 | 732.5 | 1300 | 800.3 | |
kW | 2110 | 1541 | 2813 | 1786 | 3516 | 2559 | 3868 | 2487 | 4219 | 2575 | 4571 | 2814 | ||
輸入功率 | kW | 430.6 | 359.4 | 556.3 | 416.7 | 659.9 | 564.7 | 705.7 | 549.4 | 766.5 | 563.4 | 828.8 | 595.3 | |
效率 | kW/Ton | 0.718 | 0.820 | 0.695 | 0.820 | 0.660 | 0.776 | 0.642 | 0.777 | 0.639 | 0.769 | 0.638 | 0.744 | |
COP | W/W | 4.90 | 4.29 | 5.06 | 4.29 | 5.33 | 4.53 | 5.48 | 4.53 | 5.50 | 4.57 | 5.51 | 4.73 | |
運行電流 | A | 747 | 645 | 973 | 740 | 1167 | 1036 | 1251 | 1006 | 1379 | 1024 | 1498 | 1081 | |
啟動電流 | A | |||||||||||||
冷媒充注量 | kg | 449 | 449 | 449 | 449 | 727 | 727 | 727 | 727 | 703 | 703 | 748 | 748 | |
蒸 發(fā) 器 | 水量 | 389 | 389 | 518 | 518 | 648 | 648 | 712 | 712 | 777 | 777 | 842 | 842 | |
壓降 | kPa | 77 | 79 | 129 | 140 | 200 | 219 | 195 | 213 | 183 | 199 | 174 | 189 | |
配管 | mm | DN250 | DN250 | DN250 | DN250 | DN300 | DN300 | |||||||
冷 凝 器 | 水量 | 442 | 442 | 588 | 588 | 727 | 727 | 798 | 798 | 870 | 870 | 942 | 942 | |
壓降 | kPa | 42 | 42 | 94 | 94 | 73 | 73 | 71 | 71 | 64 | 64 | 108 | 110 | |
配管 | mm | DN250 | DN250 | DN300 | DN300 | DN300 | DN300 | |||||||
運輸重量 | kg | 10303 | 11178 | 13641 | 13968 | 15403 | 15887 | |||||||
運行重量 | kg | 11717 | 12713 | 15965 | 16435 | 18123 | 18712 |
運行工況:白天制冷冷凍水供回水溫度:5/10℃,冷卻水進出水溫度:32/37℃;夜晚蓄冰時冷凍水出水溫度-5.6℃,冷卻水進水溫 度30℃。 乙二醇濃度25%,蒸發(fā)器水側(cè)污垢系數(shù)0.0176℃·m2 /kW,冷凝器系水側(cè)污垢系數(shù)為0.044℃·m2 /kw
型號 | 30HXY | 30HXC | ||||||||
110B | 130B | 165B | 200B | 250B | 300B | 350B | 400B | |||
空調(diào)工況 | 制冷量 | kW | 317 | 438 | 554 | 672 | 845 | 1008 | 1175 | 1343 |
輸入功率 | kW | 71 | 98 | 122 | 138 | 185 | 210 | 250 | 278 | |
蓄冰工況 | 制冷量 | kW | 211 | 270 | 336 | 448 | 509 | 671 | 707 | 893 |
輸入功率 | kW | 69 | 94 | 119 | 134 | 179 | 202 | 242 | 268 | |
額定工況電流 | A | 131 | 171 | 213 | 241 | 323 | 367 | 437 | 486 | |
最大啟動電流 | A | 328 | 314 | 374 | 465 | 575 | 650 | 745 | 840 | |
蒸 發(fā) 器 | 流量 | 58 | 80 | 102 | 123 | 155 | 184 | 216 | 245 | |
空調(diào)工況水壓降 | kPa | 80 | 54 | 64 | 90 | 81 | 90 | 98 | 99 | |
蓄冰工況水壓降 | kPa | 139 | 96 | 109 | 103 | 76 | 106 | 107 | 116 | |
冷 凝 器 | 流量 | 67 | 92 | 116 | 138 | 177 | 209 | 245 | 277 | |
空調(diào)工況水壓降 | kPa | 37 | 57 | 55 | 64 | 77 | 59 | 66 | 85 | |
蓄冰工況水壓降 | kPa | 59 | 90 | 86 | 64 | 65 | 59 | 66 | 85 |
1.空調(diào)工況:冷凍水進出水溫度7/12℃,冷卻水進出水溫度30/35℃
2.蓄冰工況:冷凍水出水溫度-6℃,冷卻水進水溫度30℃
3.載冷劑為25%乙二醇溶液
專業(yè)名詞解釋
ICE STORAGE PACKAGED
冰蓄冷系統(tǒng)
Ice storage system
通過制冰方式,以冰的相變潛熱為主蓄存冷量的蓄冷系統(tǒng)。
The cold storage system mainly uses the phase change latent heat of ice as the cold storage capacity through icemaking.
封裝式蓄冰系統(tǒng)
Encapsulated ice storage system
將封裝蓄冷介質(zhì)的蓄冷容器密集地放置在蓄冰裝置中,由低溫載冷劑經(jīng)蓄冰裝置,使蓄冷容器內(nèi)的蓄冷介質(zhì)結(jié)冰來儲存冷量的蓄冷系統(tǒng)。
A cold storage system in which cold storage containers encapsulating the cold storage medium are denselyplaced in the ice storage device, and the cold storage medium in the cold storage container is frozen by the lowtemperature refrigerant through the ice storage device to store the cold energy.
蓄冷空調(diào)系統(tǒng)
Cold storage air conditioning system
將冷量以顯熱、潛熱的形式蓄存載某種介質(zhì)中,冰能夠載需要時釋放出冷量的空調(diào)系統(tǒng)。
The air conditioning system that stores the cooling capacity in the form of sensible heat and latent heat in acertain medium, and the ice can carry the cooling capacity when needed.
冰蓄冷經(jīng)濟價值
ICE STORAGE PACKAGED
利用晚上夜間低電價谷電蓄冷,高峰電價使用。如:某?。ㄊ校┕入姇r段電價為0.25元,峰電時段電價為1.0元,用晚上0.25元的谷電儲存冷量,白天峰電時段不開啟原空調(diào)制冷機組,直接用谷電通儲存的冷量為終端供冷,相當(dāng)于用夜間0.25元的電價抵消峰電1.0元的電價,節(jié)費率高達75%,具有良好的經(jīng)濟效益。
The night low electricity price valley electricity is used for cold storage, and the peak electricity price is used. Forexample, in a province (city), the electricity price in the valley power period is 0.25 yuan, and the electricity pricein the peak power period is 1.0 yuan. In the evening, 0.25 yuan of valley power is used to store the cooling capaci-ty. In the daytime peak power period, the original air-conditioning refrigeration unit is not started, and the storedcooling capacity of valley power is directly used for terminal cooling, which is equivalent to offsetting the electric-ity price of 1.0 yuan of peak power with 0.25 yuan of electricity at night. The cost saving rate is as high as 75%,with good economic benefits.
冰蓄冷優(yōu)勢
ICE STORAGE PACKAGED
利用地區(qū)供電政策實現(xiàn)“移峰填谷”,夜間電價低谷時制冰,日間電價高峰時將冰融化供冷。
●減少裝機容量及配套設(shè)施,降低配電工程投入。
●采用雙工況制冷機組實現(xiàn)空調(diào)工況和制冰工況,一機兩用。
●蓄冰系統(tǒng)可提供2-4℃恒定低溫供水,實現(xiàn)大溫差供冷。
The regional power supply policy is used to realize "peak shifting and valley filling". Ice is made when the electrici-ty price is low at night, and ice is melted for cooling when the electricity price is peak during the day.? Reduce installed capacity and supporting facilities, and reduce power distribution project investment.? Double working condition refrigeration unit is used to realize air conditioning working condition and icemaking working condition. One machine can be used for two purposes.? The ice storage system can provide 2-4 "℃ constant low temperature water supply to realize large temperaturedifference cooling.